HIGH VOLTAGE POWER SUPPLIES - HYN SERIES
HIGH VOLTAGE POWER SUPPLIES - HYN SERIES ,The mains voltage is transformed to high voltage potential. Either on the primary side or on the secondary side, a phase cutting circuit with thyristors is installed. The rectified voltage is smoothed by a LC-filter.
Product variants
Technical Data
Features
Datasheet
Product variants
Series | Vmax | Amax | Pmax | Width | Height | Depth | Weight |
---|---|---|---|---|---|---|---|
HYN 21000-3500 | 3.5kV | 6 A | 21kW | 600 mm | 2000mm | 800mm | 480 kg |
HYN 28000-3500 | 3.5kV | 8 A | 28kW | 600 mm | 2000mm | 800mm | 600 kg |
HYN 35000-3500 | 3.5kV | 10 A | 35kW | 600 mm | 2000mm | 800mm | 800 kg |
HYN 70000-3500 | 3.5kV | 20 A | 70kW | 1200mm | 2000mm | 800mm | 1,400kg |
HYN 21000-6500 | 6.5kV | 3 A | 21kW | 600 mm | 2000mm | 800mm | 480 kg |
HYN 28000-6500 | 6.5kV | 4 A | 28kW | 600 mm | 2000mm | 800mm | 600 kg |
HYN 35000-6500 | 6.5kV | 5 A | 35kW | 600 mm | 2000mm | 800mm | 800 kg |
HYN 70000-6500 | 6.5kV | 10 A | 70kW | 1200 mm | 2000mm | 800mm | 1,400kg |
HYN 21000-12500 | 12.5kV | 1.5 A | 21kW | 600 mm | 2000mm | 800mm | 480 kg |
HYN 28000-12500 | 12.5kV | 2 A | 28kW | 600 mm | 2000mm | 800mm | 600 kg |
HYN 35000-12500 | 12.5kV | 2.5 A | 35kW | 600 mm | 2000mm | 800mm | 800 kg |
HYN 50000-12500 | 12.5kV | 4 A | 50kW | 1200 mm | 2000mm | 800mm | 1,200kg |
HYN 7000-20000 | 20 kV | 300mA | 7 kW | 600 mm | 1500 mm | 600mm | 230 kg |
HYN 10500-20000 | 20 kV | 500mA | 10.5kW | 600 mm | 1500 mm | 600mm | 340 kg |
HYN 14000-20000 | 20 kV | 600mA | 14 kW | 600 mm | 2000mm | 800mm | 400 kg |
HYN 21000-20000 | 20 kV | 1 A | 21 kW | 600 mm | 2000mm | 800mm | 480 kg |
HYN 28000-20000 | 20 kV | 1.2 A | 28 kW | 600 mm | 2000mm | 800mm | 600 kg |
HYN 35000-20000 | 20 kV | 1.5 A | 35 kW | 600 mm | 2000mm | 800mm | 800 kg |
HYN 50000-20000 | 20 kV | 2.5 A | 50 kW | 1200mm | 2000mm | 800mm | 1,200kg |
Technical Data
Mains connection | 3 x 400V ±10% 47Hz to 53Hz +N, +PE |
Ambient temperature | 0°C to +40°C |
Setting range | from approx. 1% to 100% |
Setting resolution | ±1 x 10-4 |
Residual ripple (0-10MHz) | < 1 x 10-2pp + 100mVpp |
Recovery time | < 100ms to 500ms (depending on type) for load variations of ±10% |
Setting time at nominal load | < 100ms to 2sec (depending on type) for changes of the output voltage from 10% to 90% or 90% to 10% |
Discharge time constant for output without load | approx. 5sec. to 60sec., depending on type |
Deviation | for ±10% mains voltage variation: for no load / full load: over 8 hours under constant conditions: within the temperature range: |
Features
- Simple construction
- extremely robust
- high efficiency
- short circuit proof and unlimited operation with full current in short circuit condition
- voltage and current regulation with automatic sharp transition, control modes indicated by LEDs
- voltage and current setting with 10-turn potentiometers with precision scale; the adjusting knob can be locked
- limitation of inrush current on switching on
- suitable also for inductive and capacitive loads
- interlock loop to monitor the external load and internal loop as a standard
- elapsed-hour meter as a standard
- 3½ digit digital displays for voltage and current
Datasheet